DEHUMIDIFIERINSTALLATION & OPERATIONMANUALFor Models: DRY-10-SERIESDRY-20-SERIESDRY-25-SERIESDRY-30-SERIESDRY-40-SERIESDRY-50-SERIESOC-10-SERIE

Pagina 2 - LIMITED WARRANTY

1.6.2. Controller LocationStandard low voltage (24 volt) AC wiring, such as that used with standard air conditioning equipment, is required for the 24

Pagina 3

DryAire Systems

Pagina 4

1.8. Pool Water EvaporationThe air velocity directly above and close to the pool water surface must be kept below(10) ft. per / minute. Higher air vel

Pagina 6 - SUPPORT BASE METHOD

2.1. Ducted Air SystemsIf the ductwork is installed in an unconditioned area, then sufficient insulation should be usedto prevent condensation and hea

Pagina 7

DryAire Systems

Pagina 8 - INSTALLATION

2.5. Auxiliary Heat (Duct Heater), If RequiredIn certain climates or regions and with some pool enclosures, construction materials,additional suppleme

Pagina 9

DryAire Systems

Pagina 10

OUTDOOR LINE SIZE REQUIRED (NOT TO EXCEED 50 FT.)CONDENSER OC-10 OC-20 OC-25 OC-30 OC-35 OC-40

Pagina 12 - 2.0. Air Distribution

Only trained, qualified service technicians should attempt instal-lation, or repair of DryAire dehumidification equipment. Danger of high voltagecompo

Pagina 13 - Figure 2.1.2. Duct Layout

ELECTRICAL DATAAll specifications, descriptions, rating and productsherein are subject to change without notice orrecourse.Compressor FL

Pagina 15 - COMMERCIAL APPLICATION ONLY

208/230V 208/230V 460V1 PH 3 PH 3 PHDRY-10-VSERIESELECTRICAL DATA208/230V 208/230V 460V1 PH 3 PH 3 P

Pagina 16

DryAire Systems

Pagina 18 - REMOTE CONDENSERS

4.0. Head Pressure Controller / Remote CondenserThe capacity of an air cooled condenser will vary with the difference between the entering air dry bul

Pagina 19

MOTOR HP RPM MOTOR(ESP) (ESP) PULLEYMODEL NO. CFM 0.5" 1.0" 0.5" 1.0" 0.5" 1.0"DRY-10

Pagina 20 - ELECTRICAL DATA

6.0. Start-Up ProcedureA complete start-up will minimize problems and expensive callbacks. The start-up will be quickerand easier if the space to be d

Pagina 21

REFRIGERATION FLOW DIAGRAM27

Pagina 22

7.1. System Modes of Operation7.1.1. Dehumidification / Air Reheat ModeWhen the room air requires dehumidification and heating, the dehumidifier runsi

Pagina 23 - CONTROL WIRING DIAGRAM #1

TABLE OF CONTENTS PAGE1.0. Installation...41

Pagina 24 - IMPOR T ANT

Thermostat Set-Points7.2.3. The Honeywell® automatic change-over t-stat has a minimum 3°F dead band. Setpoint require 2°F for heat and 2°F for cool. F

Pagina 25

9.2. Six Month InspectionWITH POWER SUPPLY OFF!1. Check the blower belts in the dehumidifier and the optional remote outdoorcondenser for excessive we

Pagina 26

10.3. Evaporator Coil Freeze UpEntering air temperature too low. Raise entering air temperature.Insufficient evaporator air flow. Check system air flo

Pagina 27 - 7.0. Operational Sequence

11.0. Service Diagnosis Chart11.1. Dehumidifier RunsDEHUMIDIFIER RUNSLOW HEAD HIGH HEAD LOW SUCTIONHIGH SUCTION

Pagina 28 - SYSTEM DESIGN

11.2. Dehumidifier OffDEHUMIDIFIER OFF{CONTACTOR CLOSED}COMPRESSOR HUMS DOES NOT HUM• Refrigerant pressure not

Pagina 29 - 7.2. Power On !

12.0. Unit Operating Guidelines12.1. Controller Set-PointsIt is important to determine your comfortable set points and to avoid further controlleradju

Pagina 30 - 9.0. Maintenance Procedure

Not Recommended!2.5W or MoreIntake30° or MoreDischarge20° or LessDischargeTurnVanesW5W or More ForStatic Pressure RegainIntakeTurnVanesWDryAireDryAire

Pagina 31

14.0. Outside Air Pre-Heating RequirementsDryAire Systems require that outside air be pre-heated if mixed air temperatures inside thedehumidifier migh

Pagina 32

YOU MUST CLEAN THE SYSTEM THOROUGHLY TO PREVENT REPEATED COMPRESSOR BURNOUTS!15.1. Mild Burnouts (use new R-22)If the burnout is mild, recover the ref

Pagina 33 - DEHUMIDIFIER RUNS

DryAire FactoryModel No. ChargeR-22DRY-10 SERIES 11#DRY-20 SERIES 12# DRY-25 SERIES 17# DRY-30 SERIES 19# DRY-40 SERIE

Pagina 34 - 11.2. Dehumidifier Off

TABLE OF CONTENTS PAGE3.3. Control Wiring Diagram #1...223.4. Control Wiring Dia

Pagina 35

Start-up Report DRY-SERIES Dehumidification Systems EquipmentIn order for warranty to be valid, a start-up report must be completed and returned to th

Pagina 36 - Recommended!

W185 N11497 WHITNEY DRIVE GERMANTOWN, WI 53022(262) 250-8500 FAX (262) 250-0886 eMAIL [email protected]

Pagina 37 - 15.0. Compressor Failure

1.0 Installation1.1. Product OverviewThe DryAire dehumidifier is a very high capacity, self contained dehumidifier that is manufactured by qualified

Pagina 38

1.3. Unpacking and InspectionDryAire performs several physical inspections and multiple tests on each dehumidifier duringand after the various product

Pagina 40 - Start-up Report

Do not install a standard dehumidifier in an unconditioned space or where ambient temperatures can fall below 45°F.If you must install the dehumidifie

Pagina 41